|
HOW TO BLOW WATER
OUT OF THE LINES USING COMPRESSED AIR
CAUTION! WEAR
PROPER EYE PROTECTION! Extreme care must be taken when blowing out the
system to avoid excessive pressure which can damage valves or sprinkler
pipe or cause physical injury due to flying debris. Do not stand over any
irrigation components (pipes, sprinklers, and valves) during air blow out.
Air pressure must not exceed 50 pounds per square inch (psi) for systems with polyethylene piping, and 80 psi for systems with PVC
piping.
Local irrigation contractors usually offer this service for a reasonable
fee which may also include start-up in the Spring. Depending on how
extensive your system is and what type of equipment you have installed,
you may want to choose a professional who is fully equipped to provide
this service.
The blow out method utilizes an air
compressor with a Cubic Foot per Minute (CFM) rating of 80-100 for any
mainline of 2" or less. These types of compressors can be rented at
your local equipment rental yard.
Description: Compressed
air is used to force water through all of the irrigation system components
including the mainline pipe, sprinkler control valves, lateral pipes, and
out through the sprinkler heads. To obtain proper air volume, you will
need to rent or buy a compressor capable of providing 80 to 100 cubic feet
per minute (CFM) of air volume. During the blow
out procedure, the air
pressure must not exceed 50 pounds per square inch (psi) for poly pipe
system or 80 psi for PVC pipe systems . A pressure
regulating valve must be used to avoid over pressurization of the system.
Air volume should be high and air pressure low. This combination of high
volume and low pressure will minimize the damage that can occur during the
winterization process. It is very important to select the right air
compressor for the job. Some small shop compressors (2 hp) may not be
adequate to complete the winterization procedure properly.
If the appropriate air compressor is not
available, please call an irrigation contractor. Do not try to use an air
compressor with high pressure (120 psi) and low volume to evacuate water
from the system. It is not an acceptable
practice to allow the compressor to fill the holding tank of the
compressor and the closed mainline with high pressure air, hoping the
surge of excess pressure will compensate for the lack of compressor size
and blow the line clean upon opening the sprinkler control valve. This is a dangerous practice that places very severe stresses on all of
the components of the system. Do not run the
compressor without at least one sprinkler control valve open. This lessens the chance that the system could over pressurize. It is a
common misbelief that if the system can withstand 120 psi of water
pressure, similar air pressure will not damage the system. This is not
true! The viscosity of air is much lower than water, generating much
higher stresses that can cause severe damage to the system.
Design: There should be a
separate provision on the sprinkler system mainline for hooking up the air
hose (see item C in the diagram). This could be a quick connect fitting, a
hose bib, a
manual gate valve, a plugged "tee", or simply a capped pipe in
the line. This adapter should be located as close to the water source as
possible, but should be located after the backflow device. Compressed air
should not be blown through any backflow device. Check with your air compressor manufacturer for the correct
procedure and equipment to hook up to the sprinkler system.

Blow out procedure activating valves
Automatically
Procedure: Wear
Proper Eye Protection! Do not stand over any irrigation
components (pipe, valves, or sprinklers) during air blow out. Do not run
the air compressor without a sprinkler zone control valve being open
first, from start up to compressor shut down. Air pressure must not exceed
50 pounds per square inch (psi) for poly pipe systems and 80 psi for PVC
pipe systems.
Blow
out procedure activating sprinkler control valves from the timer:
- Close mainline sprinkler
shutoff valve. ( A )
- Relieve the water pressure on the
mainline by activating a circuit, or zone, from your timer. Activate
the circuit that is furthest from the air connection before
introducing air into the piping.
- Attach the compressor hose to the blow
out adapter. ( C )
- Set the pressure regulating valve on the
compressor to 50 psi for poly pipe systems or 80 psi for PVC pipe
systems.
- Turn on the compressor. Gradually
increase the flow of air until the sprinkler heads pop up. The amount
of flow or volume required will be dependent upon the length of the
pipe run and the number of heads.
- Sustained heat
from the compressed air may damage pipe and other components. Do not
blow any circuit more than 2 minutes at a time. Switch to
another station, or zone, by advancing the timer to the next circuit. Do not turn the timer off at any time
during this operation until the compressor is first shut off.
- In order to ensure adequate drainage of
lines, repeat the cycle two or more times, activating each zone from
the timer, until nothing more than a fine mist appears from the heads.
Many sprinklers that use plastic gears in their drive mechanisms also
use water for lubrication and cooling. If a circuit is allowed to run
with nothing but air for extended periods there is a significant risk
of damaging the drive mechanism of the sprinkler.
- After blowing out all the zones, leave
one zone on while shutting down the compressor. Turn the compressor
off at this time.
- Unhook the compressor from the adapter
to the sprinkler system mainline.
- Turn the timer to "Off".
Blow out procedure activating valves
Manually
Use this section
only if your system does not have electric remote control valves.
Procedure: Wear Proper Eye Protection! Do
not stand over any irrigation components (pipes, valves, or sprinklers)
during air blow out. Do not run the air compressor without an irrigation
control zone valve being open first, from start up to compressor shut
down.
Please refer to Blow
Out Procedure Activating Valves from Timer section before
considering this alternative. Activating the valves from the timer offers
an additional margin of safety to the procedure since you would not be
placed in close proximity to the irrigation components during the blow
out.
Blow out procedure activating valves
manually:
- Close main sprinkler shutoff valve. ( A
)
- Relieve the water pressure on the
mainline by slowly opening the manual shutoff handle on one of your
irrigation zone control valves.
- Attach the compressor hose to the blow
out adapter. ( C )
- Set the pressure regulating valve on the
compressor to 50 psi for poly pipe systems or 80 psi for PVC pipe
systems.
- Turn on the irrigation station you want
to blow out.
- Turn on the compressor. Gradually
increase the flow of air from the compressor flow valve (not from the
sprinkler control valve) until the sprinkler heads pop up. The amount
of flow or volume required will be dependent upon the length of the
pipe run and the number of heads.
- Sustained heat from the compressed air
may damage pipe and other components. Do
not blow any circuit more than 2 minutes at a time.
- After 2 minutes, turn the
compressor off, and allow all of the air to completely purge
from the compressor tank and the sprinkler system.
- Turn on the next
irrigation control valve you wish to winterize.
- Turn off the last irrigation control valve you have just blown out.
- Repeat Steps 5 through 10 until you have
completed 2 or more blow out cycles per zone. There should only be a
fine mist blowing from each station if the winterization procedure was
successful. Cycle again as needed.
- Turn the compressor off. Allow any air
in the storage tank or irrigation components to disperse before
approaching the air hose or valves.
- Unhook the compressor from the adapter
to the sprinkler mainline.
|