Wilkins 350FT DCA Backflow Preventer with SAE Male Test Cocks 1-1/2 in. FPT | WK350FT-150

SKU
WK350FT-150
Free Shipping on Orders over $149
Sales Price $575.75 Our Price $980.95 You save 41%

Wilkins 350FT 1-1/2 in. DCA With Male SAE Test Cocks

Designed for installation on water lines to protect against both backsiphonage and backpressure of polluted water into the water supply. Assembly shall provide protection where a potential health hazard does not exists.

Feature & Benefits
  • Maximum working water pressure: 175 PSI
  • Maximum working water temperature: 180 F
  • Hydrostatic test pressure: 350 PSI
  • End connections Threaded: ANSI B1.20.1

Specifications

  • The Double Check Valve Backflow Preventershall be ASSE Listed 1015, rated to 180F and supplied with full portball valves.
  • The main body shall be Bronze for sizes 3/4" & 1", andNylon for sizes 1-1/4" to 2".
  • The housing shall be reinforced Nylon andthe seat disc elastomers shall be silicone (FDA Approved).
  • The first andsecond checks shall be accessible for maintenance without removing the device from the line.
  • The Double Check Valve Backflow Preventer shall bea WILKINS Model 350.

Standards Compliance (Horizontal & Vertical)

  • ASSE Listed 1015
  • IAPMO Listed
  • CSA ertified B64.5
  • Approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California
  • UL Classified (less shut-off valves only)
  • C-UL Classified (less shut-off valves only)

Materials

  • Main valve body: Cast Bronze, ASTM B 584 (3/4-1")
  • Housing: Reinforced Nylon
  • Fasteners: Stainless Steel, 300 Series
  • Elastomers:
    • Silicone (FDA Approved)
    • Buna Nitrile (FDA Approved)
  • Internals:Delrin, NSF Listed
  • Springs: Stainless Steel, 300 series
  • Ball Valves: Cast Bronze, ASTM B 584
  • Struts: Forged Brass ASTM B 124

Typical Installation

Local codes shall govern installation requirements. To be installedin accordance with the manufacturers' instructions and the latestedition of the Uniform Plumbing Code. Unless otherwise specified, theassembly shall be mounted at a minimum of 12" (305 mm) and a maximum of30" (762 mm) above adequate drains with sufficient side clearance fortesting and maintenance. If installed below grade, be certain adequate drainage is provided to prevent the device from being submerged.

More Information
Brand Wilkins
Test Cocks 4 MALE
Max Working Pressure 175 PSI
Hydrostatic Test Pressure 350 PSI
Temperature Range 33F to 180F
Main Valve Body Materials Bronze
Elastomers Silicone
Springs Stainless Steel
Warranty 1 Year
Size 1-1/2 in.
Connection FPT
Lead Free Not Lead Free